HVAC

23

Step

Inspection

Action

8

Verify whether malfunction is in expan-

sion valve or receiver/drier. Turn A/C

switch off and air conditioner stop for 10

minutes start engine turn both A/C switch

and fan switch on. Does malfunction oc-

cur after compressor turn on?

Yes Go to next step

No

Replace condenser and vacuum refrigerant

line more than 30 minutes by vacuum pump,

and refrigerant to specified level.

(Since water

has intermixed in receiver/drier and it is satu-

rated, replacement is necessary.)

9

Verify that expansion valve heat-sensing

tube within cooling unit is positioned se-

curely and correctly is expansion valve

heat-sensing tube within cooling unit se-

curely installed in proper position?

Yes

Replace expansion valve.

(Since valve closes

too much replacement is necessary.)

No

Install heat-sensing tube securely in proper

position.

10

Inspect refrigerant lines

Is piping free of damage and cracks?

Are piping connections free of oil

grime? (visual inspection)

Are piping installation points on a/c

compressor free of gas leakage?

Are piping installation on cooling unit

free of gas leakage?

Perform gas leak inspection using gas

leak tester.

Are above items okay?

Yes Go to next step

No

If piping or an A/C component is damaged or

cracked, replace it.

11

Inspect evaporator piping connections in

cooling unit for gas leakage Are piping

connections for evaporator in cooling unit

free of gas leakage?

Yes

If the vane makes a noise, add 10ml of com-

pressor oil to the A/C compressor. Verify that

the noise is no longer heard. Adjust refriger-

ant to specified amounts.

No

If piping is damaged or cracked, replace it.

If there is no damage, go to next step.

12

Inspect evaporator piping connections in

cooling unit for looseness

Yes

Tighten connections to specified torque.

If the vane makes a noise, add 10 ml of com-

pressor oil to the A/C compressor.

Verify that the noise is no longer heard. Adjust

refrigerant to specified amounts.

No

If the vane makes a noise, add 10 ml of com-

pressor oil to the A/C compressor.

Verify that the noise is no longer heard. Re-

place O-ring on piping, adjust refrigerant to

specified amounts.

13

Inspect piping connections for looseness

Are piping connections loose?

Yes

Tighten connections to specified torque. If the

vane makes a noise, add 10ml of compressor

oil to the A/C compressor. Verify that the

noise is no longer heard.

Adjust refrigerant to specified amounts.

No

If the vane makes a noise, add 10ml of com-

pressor oil to the A/C compressor.

Verify that the noise is no longer heard. Adjust

refrigerant to specified amounts.