HVAC

29

e. REFRIGERATION CYCLE TROUBLESHOOTING

Sr.

No.

Problem

Possible Cause

Remedy

4

Refrigerant

fails to circu-

late

Condition

Air conditioner does not cool.

Symptoms in refrigerant cycle

Pressure on the low pressure side is

vacuum

Pressure on the low pressure side is

vacuum low.

Frost or dew is formed on the piping at

the front and rear side of the receiver or

the expansion valve.

Cause

Moisture or dirt in the refrigerating cycle

freezes or sticks to the expansion valve

orifice, obstructing refrigerant flow.

Gas leaking from the heat sensitizing

tube of the expansion valve obstructs re-

frigerant flow.

Diagnosis

Blocked expansion valve orifice.

Countermeasures

Allow to stand for some time

and then resume operation to

decide whether the blockage is

caused by moisture or by dirt.

If caused by moisture; remove

the moisture by evacuation,

Recharge new refrigerant to

the specified amount.

If cased by dirt; remove the

expansion valve and blow out

the dirt with compressed air. If

unable to remove the dirt, re-

place the expansion valve.

Evacuate and charge new re-

frigerant to the specified

amount. If caused by gas leak-

ing from heat sensitizing tube,

replace the expansion valve.

5

Expansion

valve mal-

functioning

(opening too

much) and

improper in-

stallation of

heat sensitiz-

ing tube.

Condition

Air conditioner does not cool effectively.

Symptoms in refrigerant cycle

Pressure on both the low and high. pres-

sure sides is high.

Frost or heavy dew is formed on the pip-

ing on the low pressure side.

Cause

The expansion valve is malfunctioning or

the heat sensitizing tube is improperly in-

stalled.

Flow control is not properly performed

Diagnosis

Excessive liquid refrigerant in the low

pressure side piping.

Expansion valve opened too far.

Countermeasures

Check the installation of the

heat sensitizing tube.

If the installation is proper, re-

place the expansion valve.

6

Faulty com-

pression of

compressor

Condition

Air conditioner does not cool.

Symptoms in refrigerant cycle

Pressure on the low pressure sides is too

high and pressure on the high pressure

side is too low.

Cause

There is leakage in the compressor

Diagnosis

Faulty compression of compressor.

Delivery valve or packing is leaking or

broken or compressor is malfunctioning.

Countermeasures

Check the compressor oil for

contamination and quantity.

Replace the compressor.