AIR CONDITIONING

6

Sr.No

.

PROBLEM / SYMPTOMS

POSSIBLE CAUSED

REMEDY

5

LOW SIDE - low (< 1.8 kg/

cm2) or Vacuum. HIGH SIDE -

HIGH (>28 kg/ cm2 &

discharge air slightly cool.

Clogging on HIGH

side.(Clogging between

Compressor Outlet &

evaporator inlet)

1. Discharge the system.

2. Change the filter drier

cartridge & clogged tube.

3. Evacuate the system

4. Charge refrigerant gas & oil

qty.

5. Check performance by

ODT/ CDT.

6

1) LOW SIDE - high (> 3.5 kg/

cm2). HIGH SIDE - LOW (< 28

kg/ cm2 2) Discharge air is

warm 3) Compressor - Noisy

4) Discharge Hose - Cool

Compressor Malfunctioning,

internal damage to

compressor

1. Discharge the system.

2. Change the Compressor &

Filter Drier cartridge

3. Evacuate the system

4. Charge refrigerant gas & oil

qty.

5. Check performance by

ODT/CDT.

Blockage in Suction Hose

1. Discharge the system.

2. Change the Suction pipe.

3. Evacuate the system

4. Charge refrigerant gas & oil

qty.

5. Check performance by

ODT/ CDT.

7

Line to condenser is

excessively hot OR

Compressor clutch is not

rotating OR Compressor clutch

slippage

Restricted flow of refrigerant

in system between

Compressor to Condenser

1. Discharge the system.

2. Change the Filter Drier

Cartridge. Remove the

restriction.

3. Evacuate the system

4. Charge refrigerant gas & oil

qty.

5. Check performance by

ODT/ CDT.

8

Compressor clutch

engagement is not satisfactory

1. Open Circuit 2. Weak

Battery 3. Faulty Clutch relay

connection 4. shorted Clutch

coil

Attend & repair

1. Discharge the system.

2. Change the Compressor

3. Evacuate the system

4. Charge refrigerant gas & oil

qty.

5. Check performance by

ODT/ CDT.