HVAC

44

REFRIGERATION CYCLE TROUBLESHOOTING

Sr.

No.

Possible Cause

Remedy

5

Expansion valve mal-

functioning (opening

too much) and im-

proper installation of

heat sensitizing tube.

Condition

x

Air conditioner does not cool effective-

ly.

Symptoms in refrigerant cycle

x

Pressure on both the low and high.

pressure sides is high.

x

Frost or heavy dew is formed on the

piping on the low pressure side.

Cause

x

The expansion valve is malfunctioning

or the heat sensitizing tube is improp-

erly installed.

x

Flow control is not properly performed

Diagnosis

x

Excessive liquid refrigerant in the low

pressure side piping.

x

Expansion valve opened too far.

Countermeasures

x

Check the installation of

the heat sensitizing tube.

x

If the installation is proper,

replace the expansion

valve.

6

Faulty compression of

compressor

Condition

x

Air conditioner does not cool.

Symptoms in refrigerant cycle

x

Pressure on the low pressure sides is

too high and pressure on the high

pressure side is too low.

Cause

x

There is leakage in the compressor

Diagnosis

x

Faulty compression of compressor.

x

Delivery valve or packing is leaking or

broken or compressor is malfunction-

ing.

Countermeasures

x

Check the compressor oil

for contamination and

quantity.

x

Replace the compressor.