HVAC

37

HVAC

Step

Inspection

Action

13

Inspect piping connections for

looseness Are piping connections

loose?

Yes

Tighten connections to specified torque. If the

vane makes a noise, add 10ml of compressor

oil to the A/C compressor. Verify that the noise

is no longer heard.

Adjust refrigerant to specified amounts.

No

If the vane makes a noise, add 10ml of com-

pressor oil to the A/C compressor.

Verify that the noise is no longer heard. Adjust

refrigerant to specified amounts.

14

Verify whether malfunction is in

expansion valve, air mix and

compressor oil or elsewhere Does

UHIULJHUDQW¶V KLJK

-pressure value

hardly increases?

Yes

Go to next step.

(Pressure hardly increases.)

No

Go to step 17.

15

Verify whether a malfunction is in

compressor oil amount and a/c

compressor or elsewhere when

engine is racing, Does high-

pressure value increase?

Yes

Return to step 3.

No

Go to next step

16

Verify whether malfunctions is in

compressor oil amount or a/c

compressor after compressor oil

is replenished each 10 ml, Does

high-pressure value increase?

Yes

Troubleshooting completed.

(Explain to cus-

tomer that cause was insufficient compressor

oil.)

No

Replace A/C compressor.

(Cause is defective

AC compressor)

17

Verify whether malfunction is in

expansion valve or elsewhere Is

only refrigerant low-pressure val-

ue high?

Yes

Go to step 20.

No

Go to next step

18

Verify that air mix is installed se-

curely and properly Are heater

XQLW¶V DLU PL[ OLQNV DLU PL[ FUDQNV

and air mix rods securely and

properly installed?

Yes

Go to next step

No

Repair or install links, cranks and rods securely

in proper position.

19

Verify that expansion valve heat-

sensing tube within cooling unit is

positioned securely and correctly

Is expansion valve heat-sensing

tube within cooling unit securely

installed in proper position?

Yes

Replace expansion valve, then go to next step.

(Since valve opens too much, replacement is

necessary.)

No

Install heat-sensing tube securely in proper po-

sition, then go to next step.

20

Verify that malfunction symptom

occurs after repair Does cool air

blow out?

(Are results of refriger-

ant system performance test

okay?)

Yes

Troubleshooting completed.

Explain repairs to customer.

No

Recheck malfunction symptoms, then repeat

from step 1 if malfunction recurs.