HVAC 41 5 Expansion valve mal- functioning (opening too much) and improp- er installation of heat sensitizing tube. Air conditioner does not cool effectively. Symptoms in refrigerant cycle Pressure on both the low and high. pressure sides is high. Frost or heavy dew is formed on the piping on the low pressure side. Cause The expansion valve is malfunctioning or the heat sensitizing tube is improper- ly installed. Flow control is not properly performed Diagnosis Excessive liquid refrigerant in the low pressure side piping. Expansion valve opened too far. Countermeasures Check the installation of the heat sensitizing tube. If the installation is proper, replace the expansion valve. 6 Faulty compression of compressor Condition Air conditioner does not cool. Symp- toms in refrigerant cycle. Pressure on the low pressure sides is too high and pressure on the high pres- sure side is too low. Cause There is leaking in the compressor . Diagnosis Faulty compression of compressor. Delivery valve or packing is leaking or broken or compressor is malfunction- ing. Countermeasures Check the compressor oil for contamination and quantity. Replace the compressor.