e. REFRIGERATION CYCLE TROUBLESHOOTING

Sr.

No.

Problem

Possible Cause

Remedy

4

Refrigerant fails

to circulate

Condition

29. Air conditioner does not cool.

Symptoms in refrigerant cycle

30. Pressure on the low pressure side is

vacuum

31. Pressure on the low pressure side is

vacuum low.

32. Frost or dew is formed on the piping at

the front and rear side of the receiver or

the expansion valve.

Cause

33. Moisture or dirt in the refrigerating cycle

freezes or sticks to the expansion valve

orifice, obstructing refrigerant flow.

34. Gas leaking from the heat sensitizing

tube of the expansion valve obstructs

refrigerant flow.

Diagnosis

35. Blocked expansion valve orifice.

Countermeasures

36. Allow to stand for some time

and then resume operation to

decide whether the blockage

is caused by moisture or by

dirt. If caused by moisture;

remove the moisture by evac-

uation, Recharge new

refrigerant to the specified

amount.

37. If cased by dirt; remove the

expansion valve and blow out

the dirt with compressed air. If

unable to remove the dirt, re-

place the expansion valve.

Evacuate and charge new re-

frigerant to the specified

amount. If caused by gas

leaking from heat sensitizing

tube, replace the expansion

valve.

5

Expansion

valve malfunc-

tioning

(opening too

much) and im-

proper

installation of

heat sensitizing

tube.

Condition

38. Air conditioner does not cool effectively.

Symptoms in refrigerant cycle

39. Pressure on both the low and high.

pressure sides is high.

40. Frost or heavy dew is formed on the

piping on the low pressure side.

Cause

41. The expansion valve is malfunctioning

or the heat sensitizing tube is improper-

ly installed.

42. Flow control is not properly performed

Diagnosis

43. Excessive liquid refrigerant in the low

pressure side piping.

44. Expansion valve opened too far.

Countermeasures

45. Check the installation of the

heat sensitizing tube.

46. If the installation is proper,

replace the expansion valve.

6

Faulty com-

pression of

compressor

Condition

47. Air conditioner does not cool.

Symptoms in refrigerant cycle

48. Pressure on the low pressure sides is

too high and pressure on the high pres-

sure side is too low.

Cause

49. There is leakage in the compressor

Diagnosis

50. Faulty compression of compressor.

51. Delivery valve or packing is leaking or

broken or compressor is malfunctioning.

Countermeasures

52. Check the compressor oil for

contamination and quantity.

53. place the compressor.