HVAC

36

REFRIGERATION CYCLE TROUBLESHOOTING

Sr.

No.

OCCURANCE

POSSIBLE CAUSE

REMEDY

5

Expansion valve malfunc-

tioning (opening too

much) and improper in-

stallation

of

heat

sensitizing tube.

Condition

Air conditioner does not cool effective-

ly.

Symptoms in refrigerant cycle

Pressure on both the low and high.

pressure sides is high.

Frost or heavy dew is formed on the

piping on the low pressure side.

Cause

The expansion valve is malfunctioning

or the heat sensitizing tube is improp-

erly insstalled.

Flow control is not properly performed

Diagnosis

Excessive liquid refrigerant in the low

pressure side piping.

Expansion valve opened too far.

Countermeasures

Check the installation of the

heat sensitizing tube.

If the installation is proper,

replace the expansion

valve.

6

Faulty compression of

compressor

Condition

Air conditioner does not cool. Symp-

toms in refrigerant cycle

Pressure on the low pressure sides is

too high and pressure on the high

pressure side is too low.

Cause

There is leaking in the compressor

Diagnosis

Faulty compression of compressor.

Delivery valve or packing is leaking or

broken or compressor is malfunction-

ing.

Countermeasures

Check the compressor oil

for contamination and quan-

tity.

Replace the compressor.