HVAC

35

REFRIGERATION CYCLE TROUBLESHOOTING

Sr.

No.

OCCURANCE

POSSIBLE CAUSE

REMEDY

3

Entry of moisture in the

refrigerant cycle

Condition

Air conditioner alternately cools and

does not cool.

Symptoms in refrigerant cycle

During operation, the pressure on the

low pressure side alternates between

vacuum and normal.

Cause

The moisture mixed in the refrigerant in

the refrigerating cycle freezes in the

expansion valve orifice, blocking the

cycle. After a time, the ice melts and

normal conditions return

Diagnosis

The drier is in an oversaturated condi-

tion.

The moisture in the refrigerating cycle

freezes the expansion valve orifice,

impeding refrigerant circulation.

Countermeasures

Remove the moisture by

repeated evacuation.

Recharge new refrigerant to

the specified amount.

4

Refrigerant fails to circu-

late

Condition

Air conditioner does not cool. Symp-

toms in refrigerant cycle

Pressure on the low pressure side is

vacuum

Pressure on the low pressure side is

vacuum low.

Frost or dew is formed on the piping at

the front and rear side of the receiver

or the expansion valve.

Cause

Moisture or dirt in the refrigerating cycle

freezes or sticks to the expansion valve

orifice, obstructing refrigerant flow.

Gas leaking from the heat sensitizing

tube of the expansion valve obstructs

refrigerant flow.

Diagnosis

Blocked expansion valve orifice.

Countermeasures

Allow to stand for some

time and then resume oper-

ation to decide whether the

blockage is caused by

moisture or by dirt. If

caused by moisture; re-

move the moisture by

repeated, Recharge new re-

frigerant to the specified

amount.

If cased by dirt; remove the

expansion valve and blow

out the dirt with compressed

air. If unable to remove the

dirt, replace the expansion

valve. Evacuate and charge

new refrigerant to the speci-

fied amount. If caused by

gas leaking from heat sensi-

tizing tube, replace the

expansion valve.