HVAC

39

REFRIGERATION CYCLE TROUBLESHOOTING

Sr.

No.

Possible Cause

Remedy

1

Insufficient refrigerant

Condition

Air conditioner does not cool effectively.

Symptoms in refrigerant cycle

Pressure on both the high and low

pressure sides is low.

Air around the air outlet is slightly cold.

Cause

There is gas leakage in the refrigerating

cycle.

Diagnosis

Insufficient refrigerant in the refrigerat-

ing cycle.

Refrigerant leakage.

Countermeasures

Locate the leakage and re-

pair.

Recharge refrigerant to the

specified amount.

2

Excessive refrigerant

or insufficient conden-

ser cooling

.

Condition

Air conditioner does not cool effectively

Symptoms in refrigerant cycle.

Pressure on both the high and low

pressure sides is high.

Cause

Refrigerant is overcharge in the refrig-

erating cycle causing poor cooling

performance.

Condenser cooling performance is

poor.

Fluid coupling on fan is slipping.

Diagnosis

Excessive refrigerant in the refrigerat-

ing cycle.

Overcharged refrigerant.

Poor condenser cooling performance.

Condenser fins blocked or fan belt

loose.

Slipping radiator fan fluid coupling.

Silicone oil leaking from the coupling.

Countermeasures

Clean the condenser.

Tighten the fan belt to the

correct tension.

Repair the fluid coupling and

adjust silicone oil quantity to

the proper level.

Above are all normal check

the refrigerant.

3

Entry of moisture in the

refrigerant cycle

Condition

Air conditioner alternately cools and

does not cool.

Countermeasures

Remove the moisture by

repeated evacuation.