(b) Evacuation and Recharging
1. Add refrigerant oil if necessary.
2. Evacuate the system according to the
manufactures instruction.
NOTE:
If the vacuum reading is below 700 mmHg after 15
minutes, suspect a leak in the system. Partially
recharge the system and check for leaks by using
leak detector. Check suction lines first, then run
the compressor for 5 minutes and then check the
high pressure lines.
CAUTION:
The systemmust be evacuated immediately before
recharging commences. Delay betweenEvacuation
and Recharging is not permitted.
3. Recharge the refrigerant as per instructions.
Refrigerant to be charged in the system is 380 ±
20 gms. For the vehicles fitted with ‘VALEO’
compressor, the refrigerant charge quantity is
410 + 20 gms.
4. If the full charge has not been accepted by the
system, start the engine and run it at 1500 rev/min
for a minimum of 2 minutes. Switch ON the air
conditioning system, open the vehicle windows,
set the temperature control to cold and switch the
blower to maximum speed.
5. Consult Refrigerant Station Manual for correct
procedure to complete the charge.
6. Carry out the air conditioning system performance
test.