HVAC

41

5

Expansion valve mal-

functioning (opening

too much) and improp-

er installation of heat

sensitizing tube.

Air conditioner does not cool effectively.

Symptoms in refrigerant cycle

Pressure on both the low and high.

pressure sides is high.

Frost or heavy dew is formed on the

piping on the low pressure side.

Cause

The expansion valve is malfunctioning

or the heat sensitizing tube is improper-

ly installed.

Flow control is not properly performed

Diagnosis

Excessive liquid refrigerant in the low

pressure side piping.

Expansion valve opened too far.

Countermeasures

Check the installation of the

heat sensitizing tube.

If the installation is proper,

replace the expansion valve.

6

Faulty compression of

compressor

Condition

Air conditioner does not cool. Symp-

toms in refrigerant cycle.

Pressure on the low pressure sides is

too high and pressure on the high pres-

sure side is too low.

Cause

There is leaking in the compressor .

Diagnosis

Faulty compression of compressor.

Delivery valve or packing is leaking or

broken or compressor is malfunction-

ing.

Countermeasures

Check the compressor oil for

contamination and quantity.

Replace the compressor.