HVAC

the moistureby repeated, Recharge new refrigerant

to the specified amount .

If casedby dirt; remove theexpansion valveandblow

out the dirt with compressed air. If unable to remove

the dirt, replace the expansion valve. Evacuate and

charge new refrigerant to the specified amount. If

caused by gas leaking from heat sensitizing tube,

replace the expansion valve.

5. EXPANSION VALVE MALFUNCTIONING

(OPENING TOO MUCH) AND IMPROPER

INSTALLATION OF HEAT SENSITIZING TUBE

Condition

Air conditioner does not cool effectively

Symptoms in refrigerant cycle

Pressure on both the low and high pressure

sides is high

Frost or heavy dew is formed on the piping on

the low pressure side

Cause

The expansion valve is malfunctioning or the

heat sensitizing tube is improperly installed

Flow control is not properly performed

Diagnosis

Excessive liquid refrigerant in the low pressure

side piping

Expansion valve opened too far

Countermeasures

Check the installation of the heat sensitizing

tube

If the installation is proper, replace the expansion

valve

6. FAULTYCOMPRESSIONOFCOMPRESSOR

Condition

Air conditioner does not cool

Symptoms in refrigerant cycle

Pressure on the low pressure sides is too high

and pressure on the high pressure side is too

low

Cause

There is leaking in the compressor

Diagnosis

Faulty compression of compressor

Delivery valve or packing is leaking or broken ,

or compressor is malfunctioning

Countermeasures

Check the compressor oil for contamination and

quantity

Replace the compressor