TIGOR.EV UPGRADE SERVICE MANUAL

FATC 44 REFRIGERATION CYCLE TROUBLESHOOTING Sr. No. POSSIBLE CAUSE REMEDY 1 Insufficient refrigerant Condition • Air conditioner does not cool effectively Symptoms in refrigerant cycle • Pressure on both the high and low pressure sides is low • Air around the air outlet is slightly cold Cause • There is gas leakage in the refrigerating cycle Diagnosis • Insufficient refrigerant in the refrigerating cycle • Refrigerant leakage Countermeasures • Locate the leakage and repair • Recharge refrigerant to the specified amount 2 Excessive refrigerant or insufficient condenser cooling. Condition • Air conditioner does not cool effectively Symptoms in refrigerant cycle • Pressure on both the high and low pressure sides is high. Cause • Refrigerant is overcharge in the refrigerating cycle causing poor cooling performance • Condenser cooling performance is poor. • Fluid coupling on fan is slipping. Diagnosis • Excessive refrigerant in the refrigerating cycle. • Overcharged refrigerant. • Poor condenser cooling performance. • Condenser fins blocked or fan belt loose. • Slipping radiator fan fluid coupling. • Silicone oil leaking from the coupling. Countermeasures • Clean the condenser. • Tighten the fan belt to the correct tension. • Repair the fluid coupling and adjust silicone oil quantity to the proper level. • Above are all normal check the refrigerant.