NEXON EV SERVICE MANUAL

FATC 39 iii. CLOSED DOOR TEST TEST DURATION: 10 min. INITIAL VEHICLE CONDITIONS Run the vehicle in the above condition with all doors closed for 10 min. At the end of 10 min insert the probe at the front vent and record the readings similarly insert the probe at the rear vent and record the reading. RH: Relative Humidity. NOTE  The above table is applicable if the ambient RH is 40%.  The tables are applicable ambient temperature varying from <30 °C to >40 °C. Closed Door Test Test Test Condition Ambient Temperature < 24°C (RH upto 40%) 24°C to 30° (RH upto 40%) 30°C to 35°C (RH upto 40%) 35°C to 40° (RH upto 40%) > 40°C (RH upto 40%) Stationary AC Performance Closed Door Test  Vehicle to be kept in shade  Test Duration-10 minutes  Vehicle Stationary All doors closed  Blower speed – 4th  AC switch –ON  Temp Knob- Max Cool  Vent Mode- Chest  Air intake – Recirculation mode Ambient temperature >18°C 9.5 11 12 12.8 13 For acceptable performance the measure grill temperature should lie on the line or below the line corresponding to RH