TATA PUNCH SERVICE MANUAL

HVAC (ETC) 21 Step Inspection Action 14 Verify whether a malfunction is in compressor oil amount and a/c compressor or elsewhere when engine is racing, Does high-pressure value increase? Yes Return to step 3. No Go to next step 15 Verify whether malfunctions is in compressor oil amount or a/c compressor after compressor oil is replenished each 10 ml, Does high-pressure value increase? Yes Troubleshooting completed. (Explain to customer that cause was insufficient compressor oil.) No Replace A/C compressor. (Cause is defective AC compressor) 16 Verify whether malfunction is in expansion valve or elsewhere Is only refrigerant low-pressure value high? Yes Go to step 20. No Go to next step 17 Verify that air mix is installed securely and properly Are heater unit’s air mix links, air mix cranks and air mix rods securely and properly installed? Yes Go to next step No Repair or install links, cranks and rods securely in proper position. 18 Verify that malfunction symptom occurs after repair Does cool air blow out? (Are results of refrigerant system performance test okay?) Yes Troubleshooting completed. Explain repairs to customer. No Recheck malfunction symptoms, then repeat from step 1 if malfunction recurs.