HVAC 40 REFRIGERATION CYCLE TROUBLESHOOTING Sr. No. POSSIBLE CAUSE REMEDY 1 Insufficient refrigerant Condition Air conditioner does not cool effectively Symptoms in refrigerant cycle Pressure on both the high and low pressure sides is low Air around the air outlet is slightly cold Cause There is gas leakage in the refrigerating cycle Diagnosis Insufficient refrigerant in the refrigerating cycle Refrigerant leakage Countermeasures Locate the leakage and repair Recharge refrigerant to the specified amount 2 Excessive refrigerant or insufficient condenser cooling. Condition Air conditioner does not cool effectively Symptoms in refrigerant cycle Pressure on both the high and low pressure sides is high. Cause Refrigerant is overcharge in the refrigerating cycle causing poor cooling performance Condenser cooling performance is poor. Fluid coupling on fan is slipping. Diagnosis Excessive refrigerant in the refrigerating cycle. Overcharged refrigerant. Poor condenser cooling performance. Condenser fins blocked or fan belt loose. Slipping radiator fan fluid coupling. Silicone oil leaking from the coupling. Countermeasures Clean the condenser. Tighten the fan belt to the correct tension. Repair the fluid coupling and adjust silicone oil quantity to the proper level. Above are all normal check the refrigerant.