TIGOR EV_ZIPTRON_SERVICE MANUAL

FATC 47 CLOSED DOOR TEST TEST DURATION: 10 min. INITIAL VEHICLE CONDITIONS Run the vehicle in the above condition with all doors closed for 10 min. At the end of 10 min insert the probe at the front vent and record the readings. RH: Relative Humidity. NOTE  The above table is applicable if the ambient RH is 40%.  The tables are applicable ambient temperature varying from <30 °C to >40 °C. Closed Door Test: Test Test Condition Ambient Temperature < 26°C 26°C to 32° 32°C to 35°C 35°C to 40°C > 40°C RH up to 40% (For higher humidity, refer the below graph) Stationary AC Per- formance Closed Door Test  Vehicle to be kept in shade  Test Duration-10 minutes  Vehicle Stationary and all doors closed  Blower speed – Maximum  AC switch –ON  Temp Knob- Max Cool  Vent Mode- Chest  Air intake – Recirculation mode Preferable ambient temperature >20°C 12.1 10.8 11.7 12.8 13.7 For acceptable performance the measured grill temperature should lie on the line or below the line corresponding to RH